Design Criteria
The City of Arvada design criteria is as follows
- Frost Depth = 36 inches
- Roof Snow Load = 30 PSF
- Ground Snow Load = 25 PSF
- Rainfall (for roof drain sizing) = 2.4" per hour
- Seismic Design Catagory: B
- Winter Design Temp: 1 degree F. (-17 degrees C)
- Summer Design Temp: 95 degrees F ( 20.77 degrees C)
- Termite: Slight to Moderate
- Flood Hazzards: NFIP-November 20 1972/FIRM-June 17 2003
- Air Freezing Index: 500-1000
- Mean Annual Temp: 50.5
- Decay: None to Slight
- Weathering - Severe
- Moderate Hail Exposure 1 layer roofing for Asphalt.
- Ice Barrier required
Wind Speed:
- East of Sheridan Blvd: 90 Mph/Exposure B
- West Sheridan Blvd. to Wadsworth Blvd: 100 Mph/Exposure B
- West Wadsworth Blvd. to Indiana St: 110 Mph/Exposure B
- West of Indiana St to Highway 93: 110 Mph/Exposure C
- West of Highway 93 120 Mph/Exposure C
Energy
- Climate Zone 5
- Interior Design 72 Degrees F(22 C) maximum heating
- Interior Design 75 Degrees F(25 C) minimum cooling
Insulation
- Roof
Attic: R-30
Insulation above deck: R-20
-
Walls
Wood: R-13
Mass: R-7.6
Metal Building: R-13 + R-13
Metal Frame: R-13 + R-3.8 Cont. Ins.